Prev Next Download
TF01014380100506PAIUTE PIPELINE COMPANY
TF02 1-A  2Second Revised Volume No. 1-A
TF03      590020005P126Second Revised Sheet No. 59
TF04                First Revised Sheet No. 59 
TF05Edward C. McMurtrie, Vice President/General Manager
TF06100506                          110506
			GENERAL TERMS AND CONDITIONS
				(Continued)

3.  QUALITY

    3.1  Quality of Gas Tendered by Shipper to Paiute at the Receipt 
    	 Point(s):
    	 
    	 All gas tendered by Shipper to Paiute at the Receipt 
    	 Point(s) shall conform to the following specifications:
    	 
    	 (a)  Liquids: The hydrocarbon dew point of the gas tendered 
    	      shall not exceed fifteen (15) degrees Fahrenheit as 
    	      calculated from the gas composition and shall be free 
    	      from hydrocarbons and water in their liquid state at 
    	      the temperature and pressure delivered.
    	 
    	 (b)  Hydrogen Sulfide and Total Sulfur: The gas shall 
    	      contain not more than one quarter (0.25) grain of 
    	      hydrogen sulfide per one hundred (100) cubic feet and 
    	      not more than twenty (20) grains total sulfur per one 
    	      hundred (100) cubic feet.
    	 
    	 (c)  Carbon Dioxide and Nitrogen: The gas shall contain not 
    	      more than two percent (2%) by volume of either carbon 
    	      dioxide or nitrogen individually and shall contain not 
    	      more than three percent (3%) by volume of combined 
    	      non-hydrocarbon gases including, but not limited to, 
    	      carbon dioxide, nitrogen and oxygen.
    	 
    	 (d)  Dust, Gums, Etc.: The gas shall be commercially free of 
    	      dust, gums, dirt, impurities and other solid matter.
    	 
    	 (e)  Heating Value: The total gross heating value of the gas 
    	      tendered to Paiute hereunder shall not be less than  
    	      975 Btus per cubic foot.
    	 
    	 (f)  Oxygen: The gas shall not contain in excess of 
    	      two-tenths of one percent (0.2%) by volume of oxygen, 
    	      and the parties agree to exercise every reasonable 
    	      effort to keep the gas completely free of oxygen.
    	 
    	 (g)  Temperature: The temperature of the gas tendered to 
    	      Paiute hereunder shall not exceed one hundred twenty 
    	      (120) degrees Fahrenheit.
    	 
    	 (h)  Water Vapor: The gas tendered shall not contain more 
    	      than seven (7) pounds of water in vapor phase per one 
    	      million (1,000,000) cubic feet.


Prev Next Download